The PCLC-906D Power Cable Fault locator is an easy operation device used for distance locating . It’s easy to operate,support both touch screen/button operation and with friendly interface.
shared:

 

  1. GENERAL DESCRIPTION

     

    The  PCLC-906D Power Cable Fault locator is an easy operation device used for distance locating . It’s easy to operate,support both touch screen/button operation and with friendly interface.

    Low voltage pulse mode (TDR ) can be used independently; In impulse current mode (ICM), it needs to be used with HVSG-500GN series high voltage signal generator; In the multiple impulse mode(MIM) must also be tested with PCLC-900C cable multiple impulse filter coordination; After the distance measurement is completed, the PCLD-904P series digital multifunctional cable fault pin-pointer shall be used for accurate point pinpointing. Together, they form a high-performance cable fault finding system that offers a variety of innovative features.

     

    1. FUNCTION FEATURE:

  • Multiple distance locating method:

  • Low current impulse method: apply to the locating of the low resistance fault. Short circuit fault, open circuit fault. It also can be used in the measurement of the cable length, the intermediate joints, T joints, and cable termination joint. This method also can be used to correct the wave velocity.

  • Impulse current method: apply to the high resistance fault, breakdown fault. Use the current coupler to gather signal from the earth wire  

  • Multiple impulse method: improvement of the SIM method.Waveform is clear and easy to identify, high ranging accuracy.

  • 400MHz real-time sampling

  • Advance tech.Upgrading for SIM method

  • Max. 0.1m measurement resolution,PCLC-906D has small blind zone and is special for the short cable and nearly-terminal fault cable

  • Auto measurement function

  • Automatic selection of appropriate range and gain, given fault location, easier testing.

  • Only low voltage pulse mode supports this mode.

  • Automatic calibration function

  • Automatically analyze the characteristic waveform of the fault waveform and display the possible fault location .

  • Only low voltage pulse mode (TDR) supports this mode.

  • Enhance the picture-in-picture temporary comparison function

  • PIP copy(pic. temporary storage). There'll be a main window and three temporary storage windows could check three waveform at same time.

  • Support low-voltage pulse and pulse current waveform comparison function, fault distance multi-direction verification, more accurate judgment.  

  • Overall display function

  • When the waveform zoom, the overall waveform is displayed at the same time, which is more convenient for calibration and ranging.

  • Touch screen and press key operation

  • Touch operating screen with smart gesture operation

  • Support cursor drag-drop function and double-click function,easy to locate

  • Big color LED screen, friendly interface

  • Waveform clear, especially in the multiple impulse test, multiple waveform using different colors, easier to identify

  • 8" LED screen,bright with 1500cd/m2 to view under sunshine

  • Support automatic backlight brightness adjustment function

  • Waveform storage and PC communication

  • A large number of waveforms can be stored in the machine

  • Use USB disk to export waveform data

  • Waveform storage and communication with computer.

  • Provide computer background management software to manage data dumped by U disk or online data.  

  • Power management

  • Back light weakens if no operation in 1 min and power off in 30 min. if no operation.

  • When the battery is under voltage, the instrument will automatically shut down to protect the battery.

  • Built-in Polymer Lithium-ion battery.

  • Working time could reach 10 hours for each use.

  • Solid case, light and portable.

     

     

     

      1. SPECIFICATION:

    • Working mode: low voltage pulse(TDR), pulse current(ICM), multiple pulse(MIM).

    • Signal gain adjustment range: 70dB.

    • Low voltage pulse emission voltage: 30V.

    • Measurement error: ± (0.5%×L+ 1M),L≥20m

    • Low pressure pulse pulse width: 40ns~ 20.5us

    • Highest resolution: 0.1m.

    • Maximum sampling frequency: 400MHz real-time sampling.

    • Maximum ranging range: 100km.

    • Wave speed setting range: 100m/ US ~300m/us

    • Ranging blind area: 2M.

    • Number of waveform saved: 100 pcs

    • Communication interface: USB, Bluetooth (optional)

    • Power supply: lithium-ion battery pack, nominal voltage 7.4V,6000mAh.

    • Battery power supply time: Use a fully charged polymer lithium ion battery, can last for more than 10 hours (with the battery aging, continuous service time will be reduced).

    • Charger: input AC220V, 50Hz, charging current 2A, charging time 6 hours.

    • Volume: 274×218×81mm

    • Quality: host unit 2.6kg

    • Conditions of use

      Temperature: -10℃ ~ +40℃

      Humidity: 5% ~ 90% RH (25℃)

      Altitude: H <4500m

       