1. Technical character
The control box is used of aluminum alloy structure.
It uses the new technology such as PWM pulse-wide modulation, middle frequency high voltage and high power IGBT device.
It uses voltage feedback; output stability is less than 3%.
Full range of voltage output, voltage regulating accuracy is less than 1%, the stability of voltage error is less than 1.5%, the voltage error ± (1.5% ±2 words), the current error ± (1.5% ± 2 words).
Raise voltage from zero voltage potentiometer.
The 0.75UDC/1mA function button is convenient for zinc oxide arrester test, and the accuracy is ±(2%±2words).
Over voltage protection uses dialing number set, and the error is ±2%.
High voltage cylinder is used of new materials, lightweight and sturdy. It’s coated with special insulating materials, electrical performance and moisture-proof ability is good.
The product conforms to DL / T848.1-2004 technology requirements, and passed the center test of electrical equipment quality inspection, strictly according to the enterprise standard.
2. Technical parameters
Specification
Technical Parameter | 60/5 | 120/5 | 100/10 | 160/2 | 180/2 | 200/2 | 250/2 | 100/200 3/2 | 200/300 3/2 | Others |
Output voltage (kV) | 60 | 120 | 100 | 160 | 180 | 200 | 250 | 100/200 | 200/300 |
600~800kV Produce according to the contract |
Output current (mA) | 5 | 5 | 10 | 2 | 2 | 2 | 2 | 3/2 | 3/2 | |
Output power (W) | 300 | 600 | 1000 | 320 | 360 | 400 | 500 | 400 | 600 | |
Charging current (mA) | 5.0 | 5.0 | 12.0 | 3.0 | 3.0 | 3.0 | 3.0 | 4.5/3.0 | 4.5/3.0 | |
Case weight (kg) | 4.5 | 7 | 5.3 | 4.3 | 4.3 | 4.4 | 4.5 | 4.5 | 8.1 | |
Dimension of multivoltage tube (mm) | Φ80 ×500 | Φ80 ×770 | Φ80 ×770 | Φ80 ×770 | Φ110 ×770 | Φ110 ×770 | Φ110 ×820 | Φ110 ×800 | Φ110 ×1350 | |
Height of multivoltage tube (kg) | 7.3 | 9 | 7.5 | 7.2 | 7.2 | 7.2 | 7.6 | 7.5 | 12.6 | |
HV polarity | Polarity of negative volt, zero voltage start, continuous adjustable | |||||||||
Work power | AC 220V±10%;50Hz | |||||||||
Voltage measuring accuracy | 1.0%(full scale)±1character, max resolution 0.1%kV | |||||||||
Current measuring accuracy | 1.0%(full scale)±1character, max resolution 0.1%uA | |||||||||
Over voltage rectify accuracy | ≤1.0% | |||||||||
0.75 switch over accuracy | ≤0.5% | |||||||||
Ripple factor | ≤1.0% | |||||||||
Voltage stability | Random fluctuation, when voltage change of power supply±10% ≤0.5% | |||||||||
Work manner | Intermittent service; 30min of rated load;1.1 times of rated voltage use:10min | |||||||||
Temperature | -15℃~50℃ | |||||||||
Relative humidity | When at 25℃,no more than 90%(no condensation) | |||||||||
Altitude | Below 2500m |
Control box Panel
1、Ground terminal: When testing, the grounding terminal of control box and high-voltage cylinder should be connected together, and then connected with the earth.
2、Output port is used for the connection of the control box and high-voltage cylinder . We only rotate the cable pressing plug clockwise in place when connecting, only rotate the cable plug anti-clockwise when broking.
3、Voltage setting switch: Used for setting the over-voltage protection value. The display unit of dial switch is kV, set values is 1.1 times of the test voltage.
4、Power input socket: A random configuration of power line and the power input socket. (AC voltage 220V±10%, socket with fuse.)
5、Digital voltage meter: Digital display high voltage DC output voltage.
6、Digital current meter: Digital display high voltage DC output current.
7、Power switch: Forward press, the power is on, the red lights, conversely to shutdown.
8、Yellow light button: This function is designed for zinc oxide arrester for measurement of 0.75UDc1mA. It’s effective when the green lights. After pressing the button, output voltage reduce to the original 0.75%, and keeps this state. Press the red button, red light and green light all out, high pressure cuts off and exits 0.75 times state.
9、The green button: High-voltage output button, high voltage indicator lamps. In red light state, press the green button, the green light and red light out, this means high voltage circuit is switched on, then we can raise voltage. It’s Effective that this button must be on voltage regulating potentiometer zero state. If press the green button, the green light is bright red, at the same time the red light is brighter, but release the green button, green light out and red light, it means Internal protection circuit has been working.
10、Red button: the red light shows that the power is switched on and the high voltage is cut off .In the green state ,press the red button, red light is bright, high voltage is cut off.
11、Voltage adjusting potentiometer: The potentiometer is a multi-turn potentiometer. Rotate clockwise to boost, and conversely to Step-down. The potentiometer has the function of controlling electronic zero protection, so must firstly return to zero before boosting.